Public Content Library

Antifouling Protection Drives Energy Savings 

06-27-2019 11:38

Summary

Enwave Chicago’s systems experience chronic fouling from untreated river water. Interphase’s ongoing pilot demonstrates the benefits of its technology to reduce systemic fouling and improve heat transfer in water-cooled chillers. The treated condensers achieved approach temperatures below 2°F, while the untreated chillers’ temperatures reached approximately 10°F within 6 weeks. This pilot proves long-term protection against fouling and scale deposits, and immediate heat transfer improvement which translates to lower utility spend and maintenance costs.

Track 6D: Distribution System Best Practices

Speakers

Noah Snyder, Interphase Materials


#AnnualConference
#ConferenceProceeding
#2019
#DistrictCooling
#InterphaseMaterials

Statistics
0 Favorited
8 Views
1 Files
0 Shares
3 Downloads
Attachment(s)
pdf file
6D.4_Snyder.pdf   1.84 MB   1 version
Uploaded - 06-27-2019